MDF/Data Center Room-Based EXM/BDC (Соединенные Штаты Америки - Тендер #56226199) | ||
| ||
| Для перевода текста тендера на нужный язык воспользуйтесь приложением: | ||
Страна: Соединенные Штаты Америки (другие тендеры и закупки Соединенные Штаты Америки) Номер конкурса: 56226199 Дата публикации: 06-08-2024 Источник тендера: Государственные закупки США |
||
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
1x ITEM A - One (1) 20kVA / 20kW Liebert EXM UPS (+1 Redundant), model 47SA020CBCM2 (refer to attached document for detailed specifications) System Input Voltage of 480V, 60Hz, 3 Phase, 3 wire plus ground. System Output Voltage of 208/120V, 3 Phase, 4 wire plus ground
· Fixed Capacity 20kVA UPS System
· System includes One (1) 20kVA Redundant Power Module
· 208V Native Output Voltage
· Single Input Configuration
· Transformer-Free Architecture - Efficiency up to 95% in double conversion mode
· Unity Power Factor Rating - Delivers more usable power per kVA
· Load Power Factor Support - Supports loads 0.5 lagging to unity without derating
· Energy Optimization Mode (Eco-Mode)
· 65kAIC Rating - Provides interrupting rating and labeling of 65kA
· Active Power Factor Corrected IGBT Input Converter
· PWM transistorized (IGBT) inverter
· Continuous Duty Static Bypass Switch
· Input Contacts - Dry contacts are available for functions including monitoring external breakers, on-generator
signal, and other functions
· Output Contacts - Dry contacts are available for functions including a permissive signal to maintenance bypass
SKRU, to trip external breakers, and other functions
· Generator Load Control - Suppresses battery charging reducing power demand by an external signal. Shifts unit
from Eco Mode to double conversion (if applicable), and synchronizes the inverter output with the bypass
· Automatic retransfer - Provides return to inverter power after an overload
· DSP based controls - Provides digital control of power conversion and system operation
· Backlit LCD display - Monitors power conversion, UPS operation and utility conditions. Deviations are logged for
troubleshooting
· Temperature-Compensated Charging/Battery Load Test
· Top-and-bottom-entry cable access
· Front only service access
· Local Emergency Power Off (EPO)
· LIFE™ Services for the 1st year
· IP 20 enclosure
· Casters and leveling feet
· UL and cUL Listed to UL Standard 1778 5th Edition
Additional Items Include:
· One (1) IntelliSlot Unity Dual Protocol Card; P/N: IS-UNITY-DP; Monitoring and configuration of Vertiv products
and environmental sensors through stand-alone Web UI or integration with Trellis™, Liebert Nform, LIFE™
Services. Supports third-party management systems using SNMP, Modbus or BACnet.
· One (1) IS-RELAY Relay Contact Card
Battery System, Internal to UPS Cabinet Includes:
· 22 Minutes at 20kW Load (Approximately 65 Minutes at 8kW load)
· One (1) Internal String of Enersys HX205-FR Batteries
1x ITEM B - One (1) Liebert EXM Maintenance Bypass Cabinet, model 47MBE37AC3R1 (refer to attached document for specifications)
· 3 Switching Devices (BIB,MBB,MIB)
· Key Interlock (SKRU)
· Cabinet Mounted Right Attached to UPS Cabinet with connecting cables factory supplied
· 600 MM - 23.6 inches Frame Size
· 480V/ 208V Input Transformer Included
· Front Access service design
· One (1) 225 Amp, 54 pole SqD bolt/plug-in panelboard
1x ITEM C – Vertiv Standard Factory Testing w/ Certified Test Reports
1x ITEM D – Start Up Service by Vertiv Customer Engineer – 7x24
Mandatory Service Inclusion:
**Quote must include delivery inside rigging services to the 7th floor. Loading dock and freight elevator are available.
**Quote must include rigging removal services and disposal of three existing Liebert chassis on the 7th floor room. Units will be disconnected, and battery packs will be reduced to a safe 12v potential by on-site electrician prior to delivery of Item A and Item B above.
We are with the Federal Government and tax exempt.
Shipping Address:
Jeff Gerace
Room 746, Clerk’s Office
450 Main Street
Hartford, CT 06103